22kV Vacuum break OLTC
Transformer Rating: Upto 10,000 Kva, Phase Curent Upto 200 Amps, Step Voltage Upto 550 Volts
OLTC TECHNICAL SPECIFICATION | |
MAX.VOLTAGE TO GROUND | 24 kV |
MAX.VOLTAGE BETWEEN PHASES | 24 kV |
MAX.CONTINUOUS CURRENT (amps) | 200/100 |
MAX.OPERATING STEP VOLTAGE (volts) | 275/550 |
MAX.NUMBER OF POSITIONS WITHOUT PRE SELECTOR | 9 |
MAX.NUMBER OF POSITIONS WITH PRE SELECTOR | 17 |
NUMBER OF PHASES | 3 |
MAX.VOLTAGE OVER TAPS | 4500 V |
LOCATION OF TAPS | ANYWHERE IN 22 kV WINDING |
1 MIN.RMS AC IN kV | IMPULSE kVp 1.2/50 MIC.SEC. | |
ALL LIVE PARTS TO GROUND | 50 | 125 |
BETWEEN PHASES | 50 | 125 |
BETWEEN ADJACENT CONTACTS | 20 | 40 |
OVER TAPPING RANGE | 20 | 40 |
APPROX.TOTAL WEIGHT | 450 kgs |
PACKING DIMESIONS(mm) | L-2410 X W-900 X H-1420 |